described in this chapter carefully to obtain safe and correct
measurement.
Mounting
●Use this flow switch under the specified operating pressure
range.
●Use this flow switch under the specified operating temperature
range.
●Withstand pressure is 2.25 MPa.
●Do not install a flow switch at a foothold position.
●Install a flow switch so that the flow direction agrees with the
arrow direction on the side of the body.
●Mount the body so that the bottom of the body does not face
upward.
●Provide a straight pipe length of more than eight times the pipe
diameter to upstream and downstream of the flow switch.
●
Set Display Part proper position taking the cable entry and display
position into account. Display Part rotates in 270 degree.
Installation
Piping connections
●Observe the specified tightening torque when connecting pipes.
Refer to the following table for the appropriate torque values.
●When connecting pipeline to the switch, apply a spanner to the
metal part of the piping section for the switch.
●Make sure that sealing tapes will not enter inside the pipe when
connecting pipes.
Appropriate tightening torque
(N・m)